TRANSFORMERS - Insulating Materials


Transformer Full Load Amps (FLA)

The Full Load Amps is the rated continuous current carrying capacity of a transformer at a referenced ambient temperature and allowable temperature rise.  Insulating materials are below for information.

The total temperature rise of an

 OA 65C transformer, at a maximum ambient temperature of 40C,

Is 120C.This does exceed the transformer insulation rating of 105C, and is allowed by ANSI.

The Full Load Amps label is located on the top decade at 1000 seconds. The Full Load Amps label is shown on the base
(Lowest KVA) rating of the transformer.

Table – Insulating Materials
Insulation        Maximum Temperature                         Insulating Materials Class
Y                              90C                                                       Cotton, silk, paper, wood, cellulose, fiber
Without impregnation or oil-immersion
                                                                                                 Class Y impregnated with natural resins,




A                              105C                                                     cellulose esters, insulating oils, etc.,
                                                                                                also laminated wood, varnished paper


Hybrid A               110C                                                     Insulter Insulation, Kraft paper with epoxy
Binders activated under pressure


E                              120C                                                     Synthetic-resin enamels, cotton and paper
Laminates with formaldehyde bonding
B                              130C                                                     Mica, glass fiber, asbestos, etc., with suitable
                                                                                                  bonding substance; built-up mica,glass fiber 
                                                                                                  and  asbestos laminates                                                                               

F                              155C                                                     The materials of Class B with more
Thermally-resistant bonding materials
H                             180C                                                     Glass-fiber and asbestos materials, and
Built-up mica, with appropriate Silicone resins
C                              >180C                                                  Mica, ceramics, glass, quartz, and asbestos
                                                                                               without binders or with silicone resins of super     
                                                                                                      thermal stability                                                                                

Hybrid H                  220C                                                     NOMEX insulation, varnish dipped
And vacuum pressure impregnated (VPI)

Transformer Through-Fault Damage Curve
Liquid-Immersed Transformers
Defines thermal and mechanical through-fault damage curves for liquid-immersed
Transformers,
“If fault current penetrates the limits of the thermal damage curve transformer insulation may be damaged. If fault current penetrates the limits of the mechanical damage curve cumulative mechanical damage may occur. The validity of these damage limit curves cannot be demonstrated by test, since the effects are progressive over the transformer lifetime. They are based principally on informed engineering judgment and favorable, historical field experience.”
Through-fault current is passing for the 2 to 1000 seconds.

1 comment:

  1. It's nice to find these useful and practical information in your blog.I also have some articles about the transformer oil filtration to share and discuss with you guys.

    http://oilfiltrationman.weebly.com

    such as
    Series ZY Single-Stage Vacuum Transformer Oil Purifier
    Series ZYD Double High Vacuum Transformer Oil Purifier
    Series ZYD-I Tansformer Oil Filtration and Regeneration system

    ReplyDelete