Transformer Full Load Amps (FLA)
The Full Load Amps is the rated continuous current carrying capacity of a transformer at a referenced ambient temperature and allowable temperature rise. Insulating materials are below for information.
The total temperature rise of an
OA 65∞C transformer, at a maximum ambient temperature of 40∞C,
Is 120∞C.This does exceed the transformer insulation rating of 105∞C, and is allowed by ANSI.
The Full Load Amps label is located on the top decade at 1000 seconds. The Full Load Amps label is shown on the base
(Lowest KVA) rating of the transformer.
Table – Insulating Materials
Insulation Maximum Temperature Insulating Materials Class
Y 90∞C Cotton, silk, paper, wood, cellulose, fiber
Without impregnation or oil-immersion
Class Y impregnated with natural resins,
A 105∞C cellulose esters, insulating oils, etc.,
also laminated wood, varnished paperHybrid A 110∞C Insulter Insulation, Kraft paper with epoxy
Binders activated under pressure
E 120∞C Synthetic-resin enamels, cotton and paper
Laminates with formaldehyde bonding
B 130∞C Mica, glass fiber, asbestos, etc., with suitable
bonding substance; built-up mica,glass fiber
and asbestos laminates
F 155∞C The materials of Class B with more
Thermally-resistant bonding materials
H 180∞C Glass-fiber and asbestos materials, and
Built-up mica, with appropriate Silicone resins
C >180∞C Mica, ceramics, glass, quartz, and asbestos
without binders or with silicone resins of super thermal stability
Hybrid H 220∞C NOMEX insulation, varnish dipped
And vacuum pressure impregnated (VPI)
Transformer Through-Fault Damage Curve
Liquid-Immersed Transformers
Defines thermal and mechanical through-fault damage curves for liquid-immersed
Transformers,
“If fault current penetrates the limits of the thermal damage curve transformer insulation may be damaged. If fault current penetrates the limits of the mechanical damage curve cumulative mechanical damage may occur. The validity of these damage limit curves cannot be demonstrated by test, since the effects are progressive over the transformer lifetime. They are based principally on informed engineering judgment and favorable, historical field experience.”
Through-fault current is passing for the 2 to 1000 seconds.